Model |
Power |
Manual |
EFI |
OC |
Alarm Ind |
Timed |
LV Reset |
Remote |
Alarm |
RS242/ |
Directional |
CT or |
|
|
|
Reset |
|
|
LED/Flag/LCD |
Reset |
|
Reset |
Output |
485 terml |
|
I Sensor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Battery Power |
|
|
|
|
|
|
|
|
|
|
|
|
|
EEFI MKII |
Battery |
Magnet |
Yes |
|
LED |
3/6 hour |
|
|
Opto-coupler |
|
CT |
|
|
EEFI RR MkII |
Battery |
Push button |
Yes |
|
LED |
3/6 hour |
|
Yes |
Yes |
|
|
CT |
|
BEEFI |
Battery |
Magnet |
Yes |
|
LED |
3/6 hour |
|
|
|
|
|
Integral CT |
|
No Battery power |
||||||||||||
|
NB |
No Battery |
Push button |
Yes |
|
Flag |
3 hour |
|
|
|
|
|
CT |
|
NB1 |
No Battery |
Push button |
Yes |
|
Flag |
3 hour |
Yes |
|
|
|
|
CT |
|
NB2 |
No Battery |
Push button |
Yes |
|
Flag |
3 hour |
|
|
Yes |
|
|
CT |
|
NB2LV |
No Battery |
Push button |
Yes |
|
Flag |
3 hour |
Yes |
|
Yes |
|
|
CT |
|
NB3 |
No Battery |
Push button |
Yes |
|
Flag |
3 hour |
|
Yes |
Yes |
|
|
CT |
|
Optional Battery/Transformer standing power source - not required during Alarm Mode |
||||||||||||
|
OMEGA EFI |
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard |
Batt or Tx |
Push Button |
Yes |
|
LED |
3/6 hour |
Yes |
|
Yes |
|
|
I Sensor |
|
Automation |
Batt or Tx |
Push Button |
Yes |
|
LED |
3/6 hour |
Yes |
Yes |
Yes |
|
|
I Sensor |
|
OMEGA OC/EF |
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard |
Batt or Tx |
Push button |
Yes |
Yes |
LED |
3/6 hour |
Yes |
|
Yes |
|
|
I Sensor |
|
Automation |
Batt or Tx |
Push button |
Yes |
Yes |
LED |
3/6 hour |
Yes |
Yes |
Yes |
|
|
I Sensor |
|
No Battery power |
|
|
|
|
|
|
|
|
|
|
|
|
|
OMNI-FI |
No Battery |
Push button |
Yes |
Yes |
LCD |
3 hour |
Yes |
Yes |
Yes |
Yes |
Yes |
CT |
|
Notes |
|
|
CT = Core balance CT |
|
|
I Sensor = Band Current Sensor |
|
|
Magnet = Magnet required to manually reset indicator |
|
|
Batt/Tx = Standing power required from Battery or 240/9V Transformer |
|
|
Pathfinder 360 ALPHA Selection Data |
|
|
|
|
|
Pathfinder 360 ALPHA - permanently installed overhead line fault passage indicator |
|
|
System Data |
|
|
System Voltage |
6KV thro 132KV |
|
Type of System Construction |
Wood pole - unearthed |
|
Installation Location |
3 metres below lowest conductors - symetrical between outers |
|
Type of pole top configuration |
Flat, triangular - two wire single phase or three wire three phase |
|
|
|
|
Pathfinder Enclosure Data |
Polycarbonate body and screw cap - watertight to IP67 |
|
O' ring seal material |
Nitrile - BS1806:1989 |
|
Support bracket |
Aluminium anodised |
|
Humidity seal |
0 - 100% |
|
Temperature range |
Including electronics -50 degrees C to +70 degrees C |
|
|
|
|
Power Source |
|
|
Primary Power |
1 x Lithium Thionyl Chloride 'D' Cell 16.5AH |
|
Battery Life |
10 years @20 degrees C - shelf life 15 years nominal |
|
Battery Health Check |
Hold Magnet over 'Test' area on side of Pathfinder - Flashing LED confirms OK |
|
|
|
|
Threshold Settings |
|
|
Type of fault |
Earth fault (including Sensitive EF) and Overcurrent fault |
|
Fault Current settings |
All fault current levels above 7A |
|
Initial time delay (mag inrush) |
40mS |
|
Sampling rate |
Continuous full wave sampling |
|
|
|
|
Alarm Indicators |
|
|
Main visual indication |
Xenon gas tube - 0.24 Joules of Flash |
|
Flash rate |
5 - 6 per minute |
|
Power demand |
15mA.hrs when flashing |
|
Secondary visual indication |
Ultra bright LED |
|
Power demand |
0.65mA.hrs |
|
Flashing Capacity |
up to 1000 hrs nominal at 20 degrees C |
|
|
|
|
Alarm Configuration |
|
|
Model 'S' - permanent faults only |
Alarms after fault current and loss of system volts |
|
|
Xenon Resets on restoration of HV volts or 3 hr Reset time which ever sooner |
|
|
If supply off longer than Reset Time then LED Alarms until HV voltage restored |
|
Model 'D' - Permanent & Transient faults |
Alarms after fault current and momentary or permanent loss of system volts |
|
|
Xenon Resets on restoration of HV volts or 3 hr Reset time which ever sooner |
|
|
LED begins Flashing for 24 hours after Xenon Resets |
|
Model 'F' - all faults downstream |
Alarms after fault current on one or more phases |
|
of fuses - All faults |
Xenon Flashes for 3 or (6hrs) then resets - no HV voltage reset |
|
Model 'FD' - all faults downstream |
Alarms after fault current on one or more phases |
|
of fuses - All faults |
Xenon Flashes for 3 (or 6hrs) then resets - LED begins Flashing for 24 hours |
|
|
No HV voltage reset |
|
|
|
|
Alarm Reset |
|
|
Manual - all Alarm functions |
Swipe magnet over 'Test' mark on side of Pathfinder |
|
|
Manual Reset overrides all Alarm Configurations detailed above. |
|
|
|
|
Flashing Capacity |
Typical examples |
|
Model 'S' - Xenon resets after 3 hours |
Capacity - 355 fault occasions |
|
Model 'D' - Xenon resets after 3 hours |
Capacity - 266 fault occasions |
|
& LED after 24 hours |
|
|
Rightway Pathfinder Mk8 Selection Data |
|
|
Rightway Pathfinder Mk8 - portable overhead line fault passage indicator |
|
|
System Data |
|
|
System Voltage |
6KV thro 132KV |
|
Type of System Construction |
Wood pole - unearthed |
|
Installation Location |
5 metres below lowest conductors - symetrical between outers |
|
Need not be located on pole but placed midspan on hedgerow or ground |
|
|
Attachment to pole |
Fitted to pole by Elastic Strap or Nylon Buckle strap - supplied |
|
Type of pole top configuration |
Flat, triangular - two wire single phase or three wire three phase |
|
Pathfinder Enclosure Data |
Polycarbonate body with 'O' ring seal |
|
Control switches Watertight |
|
|
Whole enclosure seal rated IP65 |
|
|
Power Source |
|
|
Primary Power |
1 x Lithium Thionyl Chloride Cell 3.6V 2.2AH |
|
Battery Life |
6 - 10 years @20 degrees C depending on usage |
|
Battery Health Check |
Auto health check every time unit switched 'On' |
|
Threshold Settings |
|
|
Type of fault |
Earth fault and Overcurrent fault |
|
Fault Current settings |
All fault current levels above14A (High sensitivity) and 70A (Low sensitivity) |
|
Initial time delay (mag inrush) |
40mS |
|
Alarm Indicators |
|
|
Main visual indication |
Bright RED Flag |
|
Power demand |
40 microamps in Alert State only |
|
Alarm Reset |
|
|
Manual |
Manual Reset only by Switching Unit OFF |