Earth Fault Indicator Alpha 360 |
Mk8 |
Electronic FPI |
|
Alpha |
Pathfinder
Mk 8 |
EEFI |
|
Rightway Pathfinder Mk8 Selection Data |
|
|
|
|
Rightway Pathfinder Mk8 - portable overhead
line fault passage indicator |
|
System Data |
|
|
System Voltage |
6KV thro 132KV |
|
Type of System Construction |
Wood pole - unearthed |
|
Installation Location |
5 metres below lowest conductors - symetrical between outers |
|
|
Need not be located on pole but placed midspan on hedgerow or
ground |
|
Attachment to pole |
Fitted to pole by Elastic Strap or Nylon Buckle strap - supplied |
|
Type of pole top configuration |
Flat, triangular - two wire single phase or three wire three phase |
|
|
|
|
Pathfinder Enclosure Data |
Polycarbonate body with 'O' ring seal |
|
|
Control switches Watertight |
|
|
Whole enclosure seal rated IP65 |
|
|
|
|
Power Source |
|
|
Primary Power |
1 x Lithium Thionyl Chloride Cell 3.6V 2.2AH |
|
Battery Life |
6 - 10 years @20 degrees C depending on usage |
|
Battery Health Check |
Auto health check every time unit switched 'On' |
|
|
|
|
Threshold Settings |
|
|
Type of fault |
Earth fault and Overcurrent fault |
|
Fault Current settings |
All fault current levels above14A (High sensitivity) and 70A (Low
sensitivity) |
|
Initial time delay (mag inrush) |
40mS |
|
|
|
|
Alarm Indicators |
|
|
Main visual indication |
Bright RED Flag |
|
Power demand |
40 microamps in Alert State only |
|
|
|
|
Alarm Reset |
|
|
Manual |
Manual Reset only by Switching Unit OFF |
|
|
|