Earth Fault Indicator Alpha 360 Mk8 Electronic FPI
Alpha Pathfinder Mk 8 EEFI
Pathfinder 360 ALPHA Selection Data  
   
Pathfinder 360 ALPHA - permanently installed overhead line fault passage indicator  
System Data    
System Voltage 6KV thro 132KV  
Type of System Construction Wood pole - unearthed  
Installation Location 3 metres below lowest conductors - symetrical between outers  
Type of pole top configuration Flat, triangular - two wire single phase or three wire three phase  
   
Pathfinder Enclosure Data Polycarbonate body and screw cap - watertight to IP67  
O' ring seal material Nitrile - BS1806:1989  
Support bracket Aluminium anodised  
Humidity seal 0 - 100%  
Temperature range Including electronics -50 degrees C to +70 degrees C  
   
Power Source    
Primary Power 1 x Lithium Thionyl Chloride 'D' Cell 16.5AH  
Battery Life 10 years @20 degrees C - shelf life 15 years nominal  
Battery Health Check Hold Magnet over 'Test' area on side of Pathfinder - Flashing LED confirms OK  
   
Threshold Settings    
Type of fault Earth fault (including Sensitive EF) and Overcurrent fault   
Fault Current settings All fault current levels above 7A  
Initial time delay (mag inrush) 40mS  
Sampling rate Continuous full wave sampling  
   
Alarm Indicators    
Main visual indication Xenon gas tube - 0.24 Joules of Flash  
Flash rate 5 - 6 per minute  
Power demand 15mA.hrs when flashing  
Secondary visual indication Ultra bright LED  
Power demand 0.65mA.hrs  
Flashing Capacity up to 1000 hrs nominal at 20 degrees C  
   
Alarm Configuration    
Model 'S' - permanent faults only Alarms after fault current and loss of system volts   
Xenon Resets on restoration of HV volts or 3 hr Reset time which ever sooner  
If supply off longer than Reset Time then LED Alarms until HV voltage restored  
Model 'D' - Permanent & Transient faults Alarms after fault current and momentary or permanent loss of system volts   
Xenon Resets on restoration of HV volts or 3 hr Reset time which ever sooner  
LED begins Flashing for 24 hours after Xenon Resets  
Model 'F' - all faults downstream  Alarms after fault current on one or more phases  
of fuses - All faults Xenon Flashes for 3 or (6hrs) then resets - no HV voltage reset  
Model 'FD' - all faults downstream  Alarms after fault current on one or more phases  
of fuses - All faults Xenon Flashes for 3 (or 6hrs) then resets - LED begins Flashing for 24 hours  
No HV voltage reset  
   
Alarm Reset     
Manual - all Alarm functions Swipe magnet over 'Test' mark on side of Pathfinder  
Manual Reset overrides all Alarm Configurations detailed above.  
   
Flashing Capacity  Typical examples   
Model 'S' - Xenon resets after 3 hours Capacity - 355 fault occasions  
Model 'D' - Xenon resets after 3 hours  Capacity - 266 fault occasions  
& LED after 24 hours    
 
Contact Ian Bowden or Trevor Newman at the Dorking Office